MIT485 EN Specifications |
| Accuracies quoted are at 20 degrees C |
| Nominal testing Insulation voltages |
MIT400 - 250, 500, & 1000 Volts
MIT415 - 50, 100, 250, & 500 Volts MIT410, 420, & 430 - 50, 100, 250, 500, & 1000 Volts MIT480 - 50 & 100 Volts MIT481 & 485 - 50, 100, 250, 500, & 1000 Volts MIT40X - 10 - 100 Volts variable (1 Volt increments) |
| Resistance range for Insulation |
MIT400 - 20 GigaOhms MIT410 -100 GigaOhms
MIT415 - 50 GigaOhms MIT420 & 430 - 200 GigaOhms MIT480 - 100 GigaOhms MIT481 & 485 - 200 GigaOhms MIT40X - 20 GigaOhms |
| Range of Full Scale Accuracies |
1000 volts +/-3 percent +/-2 dgts +/-0.2 percent per GOhms 500 volts +/-3 percent +/-2 dgts +/-0.4 percent per GOhms 250 volts +/-3 percent +/-2 dgts +/-0.8 percent per GOhms
100 volts +/-3 percent +/-2 dgts +/-2.0 percent per GOhms 50 volts +/-3 percent +/-2 dgts +/-4.0 percent per GOhms 10 volts +/-3 percent +/-2 dgts +/-2.0 percent per 100 MegaOhms |
| Analog range |
1 GOhms full-scale |
| Short Circuit (Current) |
2 milliAmps +0 percent -50 percent |
| Terminal V |
-0 percent +20 percent +/-1 Volt |
| Load Test Current |
1 milliAmp at minimum pass val. insulation specified per IEC364, HD384 & BS7671, 2 milliAmps maximum |
| Operating range EN61557 |
0.10 M 1/2 - 1 GOhms |
| Leakage Current |
10 percent +/-3 dgts |
| Voltage display |
3 percent +/-3 dgts +/-0.5 percent rated voltage |
| (PI) Polarization Index |
10 min/1 minute ratio |
| (DAR) Dielectric Absorption Ratio |
60 sec. / 30 sec. ratio |
| Notes |
1 - Ranges measure from 0 M 1/2 upwards 2 - Above specs. only apply to high-quality silicone test leads being used |
| Continuity Testing |
| Measurements |
.01 1/2 - 99.9 1/2 (0 - 100 1/2 analog scale) |
| Accuracy |
+/-3 percent +/-2 dgts (0 - 100 Ohms) |
| Voltage for Open circuit |
5 Volts +/-1 Volt |
| Testing current |
200 milliAmps (–0 milliAmps +20 milliAmps) (.01 1/2 to 9.99 Ohms) 20 milliAmps (+/-1 milliAmps ) (10 1/2 - 99.9 Ohms) |
| 0 offset @ probe tips |
.10 Ohms typ. |
| Zeroing for Lead resistance |
9.00 Ohms max. |
| Buzzer |
Variable limits of 1, 2, 5,10, & 20 Ohms |
| Resistances |
| Measurement |
0.01 kOhms to 1000 kOhms (0 - 1 MOhms analog scale) |
| Accuracy |
+/-3 percent +/-2 dgts Open-circuit V - 5 Volts +/-1 Volts Short-circuit current 20 microAmps +/- 5 microAmps |
| Voltage range |
0 - 600 Volts DC +/-2 percent +/-2 dgts 10 milliVolts - 600 Volts TRMS sinusoidal (40 - 400 Hertz) +/-2 percent +/-2 dgts 0 - 1000 Volts Analog scale input level Unspecified 0 to 10 milliVolts (40 - 400 Hertz)
For non sinusoidal waveform, additional specifications apply - +/-3 percent +/-2 dgts 101 milliVolts to 600 Volts TRMS & +/-8 percent +/-2 dgts 10 milliVolts - 100 milliVolts TRMS |
| Voltmeter Default |
Operates @ > 25 Volts AC or DC any range but OFF |
| Freq. (MIT410 & 480 excluded) |
40 to 450 Hertz (40 to 99.9 Hertz) +/-0.5 percent +/-1 digit (100 - 450 Hertz) |
|
Capacitance measurements for the MIT420, 430, 430-TC2, 481 & 485 |
| Range |
100 pFarads - 10 µFarads |
| Accuracy |
+/- 5 percent +/- 2 dgts |
|
Distance using capacitance - MIT481 & 485
Arithmetic conversions from capacitance measurements for Default capacitance - 50 nanoFarads / meter |
| Range |
40 - 60 nanoFarads / meter |
| Result storage (not included on the MIT400, 410, 420, 410-TC2, 480, or 40X) |
| Capacity |
over 1000 testing results |
| Downloading |
wireless Bluetooth for the MIT430, 430-TC2, & 485 only |
| Bluetooth Class Type |
Class-II |
| Range |
10 meters |
| Power |
| Supply |
5 - 1.5 Volt cells type-IEC LR6(HP7, MN1500, AM3 R6HP, AA) NiMH Alkaline rechargeable batteries can be used Life of battery - 2200 tests (insulation) w/ 5 second duty cycle ON -55 seconds OFF at 1000 Volts into 1 MOhm |
| Size |
| Unit |
220mm x 92mm x 50mm (8.66 x 3.63 x 1.97 inches) |
| Unit and case |
456mm x 178mm x 89mm (18 x 7 x 3.5 inches) |
| Weight |
| Unit only |
590 grams (20.73 ounces)
775 grams (27.22 ounces) w/ boot |
| Unit and case |
1.75 kilograms (3.86 pounds) |
| Fuse |
Use 500 milliAmps only (FF) 1000 Volts 32 x 6 millimeter ceramic fuse, HBC high-breaking capacity 50 kiloAmps min. Glass fuse MUST NOT be used |
| Safety |
EN 61010-1 (1995) compliant to 600 Volts phase - earth, Cat IV. Refer to the safety warnings included |
| EMC |
IEC 61326 compliant incl. amendment #1 |
| Temp. effects |
| Temp. coefficient |
< .1 & Omega / deg. C to 1 G & Omega max. |
| Environmental |
| Operation range |
-10 to 55 deg. C |
| Humidity |
90 percent RH @ 40 deg. C maximum |
| Storage temp. range |
-25 to 70 deg. C |
| Calibration Temp. |
+20 deg. C |
| Max. altitude |
2000 meters |
| Water & Dust protection |
IP54 Protection against dust & splashing water |